Eight
rules to follow:
- Standard Size of Transformer (IEEE/ANSI 57.120)
- Standard Size of Motor (HP)
- Approximate RPM of Motor
- Motor Line Voltage
- Motor Starting Current
- Motor Starter
- Impedance of Transformer (As per IS 2026)
- Standard Size of Transformer
Single Phase Transformer
|
Three Phase Transformer
|
5KVA, 10KVA, 15KVA, 25KVA,
37.5KVA, 50KVA, 75KVA, 100KVA, 167KVA, 250KVA, 333KVA, 500KVA, 833KVA,
1.25KVA, 1.66KVA, 2.5KVA, 3.33KVA, 5.0KVA, 6.6KVA, 8.3KVA, 10.0KVA, 12.5KVA,
16.6KVA, 20.8KVA, 25.0KVA, 33.33KVA
|
3KVA, 5KVA, 9KVA, 15KVA, 30KVA,
45KVA, 75KVA, 112.5KVA, 150KVA, 225KVA, 300KVA, 500KVA, 750KVA, 1MVA, 1.5MVA,
2MVA, 2.5MVA, 3.7MVA, 5MVA, 7.5MVA, 10MVA, 12MVA, 15MVA, 20MVA, 25MVA, 30MVA,
37.5MVA, 50MVA, 60MVA, 75MVA, 100MVA
|
2.
Standard Size of Motor (HP)
Electrical Motor (HP)
|
1, 1.5, 2, 3, 5, 7.5, 10, 15, 20,
30, 40, 50, 60, 75, 100, 125, 150, 200, 250, 300, 400, 450, 500, 600, 700,
800, 900, 1000, 1250, 1250, 1500, 1750, 2000, 2250, 3000, 3500 and 4000
|
3.
Approximate RPM of Motor
HP
|
RPM
|
<
10 HP
|
750
RPM
|
10
HP to 30 HP
|
>600
RPM
|
30
HP to 125 HP
|
500
RPM
|
125
HP to 300 HP
|
375
RPM
|
4.
Motor Line Voltage
Motor (KW)
|
Line Voltage
|
<
250 KW
|
>440
V (LV)
|
150
KW to 3000KW
|
2.5
KV to 4.1 KV (HV)
|
200
KW to 3000KW
|
3.3
KV to 7.2 KV (HV)
|
1000
KW to 1500KW
|
6.6
KV to 13.8 KV (HV)
|
5.
Motor Starting Current
Supply
|
Size of Motor
|
Max. Starting Current
|
1
Phase
|
<
1 HP
|
6
X Motor Full Load Current
|
1
Phase
|
1
HP to 10 HP
|
3
X Motor Full Load Current
|
3
Phase
|
10
HP
|
2
X Motor Full Load Current
|
3
Phase
|
10
HP to 15 HP
|
2
X Motor Full Load Current
|
3
Phase
|
>
15 HP
|
1.5
X Motor Full Load Current
|
Starter
|
HP or KW
|
Starting Current
|
Torque
|
DOL
|
<13
HP (11KW)
|
7
X Full Load Current
|
Good
|
Star-Delta
|
13
HP to 48 HP
|
3
X Full Load Current
|
Poor
|
Auto TC
|
>
48 HP (37 KW)
|
4
X Full Load Current
|
Good/
Average
|
VSD
|
0.5
to 1.5 X Full Load Current
|
Excellent
|
|
Motor > 2.2KW Should not
connect direct to supply voltage if it is in Delta winding
|
Electrical Thumb Rules For:
- Cable Capacity
- Current Capacity of Equipment
- Earthing Resistance
- Minimum Bending Radius
- Insulation Resistance
- Lighting Arrestor
- Transformer
- Diesel Generator
- Current Transformer
- Quick Electrical Calculation
Cable
Capacity
- For Cu Wire Current Capacity (Up to 30 Sq.mm) = 6X Size of Wire in Sq.mm
Ex. For 2.5 Sq.mm = 6×2.5 = 15 Amp, For 1 Sq.mm = 6×1 = 6 Amp, For 1.5 Sq.mm = 6×1.5 = 9 Amp - For Cable Current Capacity = 4X Size of Cable in Sq.mm, Ex. For 2.5 Sq.mm = 4×2.5 = 9 Amp.
- Nomenclature for cable Rating = Uo/U
- where Uo = Phase-Ground Voltage, U = Phase-Phase Voltage, Um = Highest Permissible Voltage
Current Capacity of Equipment
- 1 Phase Motor draws Current = 7Amp per HP.
- 3 Phase Motor draws Current = 1.25Amp per HP.
- Full Load Current of 3 Phase Motor = HPx1.5
- Full Load Current of 1 Phase Motor = HPx6
- No Load Current of 3 Phase Motor = 30% of FLC
- KW Rating of Motor = HPx0.75
- Full Load Current of equipment = 1.39xKVA (for 3 Phase 415Volt)
- Full Load Current of equipment = 1.74xKw (for 3 Phase 415Volt)
Earthing
Resistance
- Earthing Resistance for Single Pit = 5Ω, Earthing Grid = 0.5Ω
- As per NEC 1985 Earthing Resistance should be < 5Ω.
- Voltage between Neutral and Earth <= 2 Volt
- Resistance between Neutral and Earth <= 1Ω
- Creepage Distance = 18 to 22mm/KV (Moderate Polluted Air) or
- Creepage Distance = 25 to 33mm/KV (Highly Polluted Air)
Minimum
Bending Radius
- Minimum Bending Radius for LT Power Cable = 12 x Dia of Cable.
- Minimum Bending Radius for HT Power Cable = 20 x Dia of Cable.
- Minimum Bending Radius for Control Cable = 10 x Dia of Cable.
Insulation
Resistance
- Insulation Resistance Value for Rotating Machine = (KV+1) MΩ.
- Insulation Resistance Value for Motor (IS 732) = ((20xVoltage (L-L)) / (1000+ (2xKW)).
- Insulation Resistance Value for Equipment (<1KV) = Minimum 1 MΩ.
- Insulation Resistance Value for Equipment (>1KV) = KV 1 MΩ per 1KV.
- Insulation Resistance Value for Panel = 2 x KV rating of the panel.
- Min Insulation Resistance Value (Domestic) = 50 MΩ / No of Points. (All Electrical Points with Electrical fitting & Plugs). Should be less than 0.5 MΩ
- Min Insulation Resistance Value (Commercial) = 100 MΩ / No of Points. (All Electrical Points without fitting & Plugs).Should be less than 0.5 MΩ.
- Test Voltage (A.C) for Meggering = (2X Name Plate Voltage) +1000
- Test Voltage (D.C) for Meggering = (2X Name Plate Voltage).
- Submersible Pump Take 0.4 KWH of extra Energy at 1 meter drop of Water.
Lighting
Arrestor
Arrestor have Two Rating:
- MCOV=Max. Continuous Line to Ground Operating Voltage.
- Duty Cycle Voltage. (Duty Cycle Voltage > MCOV).
Transformer
- Current Rating of Transformer = KVA x 1.4
- Short Circuit Current of T.C /Generator = Current Rating / % Impedance
- No Load Current of Transformer =< 2% of Transformer Rated current
- Capacitor Current (Ic) = KVAR / 1.732xVolt (Phase-Phase)
- Typically the local utility provides transformers rated up to 500kVA For maximum connected load of 99kW,
- Typically the local utility provides transformers rated up to 1250kVA For maximum connected load of 150kW.
- The diversity they would apply to apartments is around 60%
- Maximum HT (11kV) connected load will be around 4.5MVA per circuit.
- 4No. earth pits per transformer (2No. for body and 2No. for neutral earthing),
- Clearances, approx.1000mm around TC allow for transformer movement for replacement.
Diesel
Generator
- Diesel Generator Set Produces = 3.87 Units (KWH) in 1 Litter of Diesel.
- Requirement Area of Diesel Generator = for 25KW to 48KW = 56 Sq.meter, 100KW = 65 Sq.meter.
- DG less than or equal to 1000kVA must be in a canopy.
- DG greater 1000kVA can either be in a canopy or skid mounted in an acoustically treated room
- DG noise levels to be less than 75dBA at 1 meter.
- DG fuel storage tanks should be a maximum of 990 Litter per unit. Storage tanks above this level will trigger more stringent explosion protection provision.
Current
Transformer
Nomenclature of CT:
- Ratio: input / output current ratio
- Burden (VA): total burden including pilot wires. (2.5, 5, 10, 15 and 30VA.)
- Class: Accuracy required for operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5, 10, 15, 20, 30).
- Accuracy Limit Factor:
- Nomenclature of CT: Ratio, VA Burden, Accuracy Class, Accuracy Limit Factor.Example: 1600/5, 15VA 5P10 (Ratio: 1600/5, Burden: 15VA, Accuracy Class: 5P, ALF: 10)
- As per IEEE Metering CT: 0.3B0.1 rated Metering CT is accurate to 0.3 percent if the connected secondary burden if impedance does not exceed 0.1 ohms.
- As per IEEE Relaying (Protection) CT: 2.5C100 Relaying CT is accurate within 2.5 percent if the secondary burden is less than 1.0 ohm (100 volts/100A).
Quick
Electrical Calculation
1HP
= 0.746 KW
|
Star Connection
|
1KW
= 1.36 HP
|
Line
Voltage = √3 Phase Voltage
|
1Watt
= 0.846 Kla/Hr
|
Line
Current = Phase Current
|
1Watt
= 3.41 BTU/Hr
|
Delta Connection
|
1KWH
= 3.6 MJ
|
Line
Voltage = Phase Voltage
|
1Cal
= 4.186 J
|
Line
Current = √3 Phase Current
|
1Tone
= 3530 BTU
|
|
85
Sq.ft Floor Area = 1200 BTU
|
|
1Kcal
= 4186 Joule
|
|
1KWH
= 860 Kcal
|
|
1Cal
= 4.183 Joule
|
No comments:
Post a Comment